Field guide · Radiator vents

Gorton C or D?

Radiator vent pick on a one-pipe job usually lands on Gorton C vs D once the runout is long or the room is cold. The decision is EDR plus runout volume, divided by the minutes you will give the radiator, matched to a published capacity — then adjusted for where the radiator sits in the building.

Estimate only

Use this as a starting point, then time the radiator and adjust. Not a substitute for licensed HVAC design.

What you are sizing

Air in the radiator + air in the runout.

Before steam can heat the iron, the air inside the radiator and its supply runout has to leave through the vent. A larger EDR and a longer or fatter runout both raise the required venting rate. Gorton C and D are the common “far / cold room” picks in Gorton's placement language; smaller letters (4, 5, 6) cover nearer radiators when the math says so.

Step 1 — EDR and construction

Read the radiator's square-foot EDR from the nameplate or a takeoff. Note the construction (tube, column, etc.) — the calculator applies published cubic-feet-of-air per square foot EDR for that type, following the Gill & Pajek worksheet approach.

Step 2 — Add the runout

Measure the runout length and nominal size from the main to the radiator valve. Convert with Schedule 40 volume per foot, same as on the main. Total air to vent is radiator air plus runout air.

Step 3 — CFM, then C vs D

required CFM = (radiator + runout cu ft) ÷ target minutes

Compare that rate to the published Gorton radiator-vent capacities at your working ounce column. Pick the smallest vent that meets the rate, then step up or down for geography: far from the boiler and cold rooms usually want more venting; near-boiler warm rooms usually want less.

Gorton's own chart describes C as for radiators farthest from the boiler and coldest rooms, and D where a large amount of air must be vented (with a hand-fired caution). Those are placement hints — the absolute CFM figures the calculator uses come from the Gill & Pajek test chart, not from converting “equal to N ordinary valves” into flow.

Work the numbers in the radiator vent sizer rather than memorizing capacities. The page also shows the source's worked example path from a modest EDR and runout into a C that the geography bump can raise to a D.

Do not oversize the thermostat radiator

Keep the vent on the radiator in the thermostat's room on the small side. If that room heats first, the thermostat thinks the whole building is warm and cuts the boiler off early — classic short-cycle complaint on one-pipe steam. Full walkthrough: don't oversize the thermostat vent.

Next step

Enter EDR, radiator type, runout, pressure, and target minutes. Read the suggested Gorton model from the cited capacity table, then apply the geography warning above.

Open radiator vent sizer

Related: Don't oversize the thermostat vent · Vent ounces and minutes · How many Gorton #2 main vents · All guides

Sources

EDR/runout method and CFM columns: Gill & Pajek (HeatingHelp PDF). Relative ratings and placement wording: Gorton product pages and air-valve chart. No invented CFM in this guide.