One-pipe steam · P0

Radiator vent sizer

Add the air in the radiator to the air in its runout, divide by how long you will give it, and match that rate to a Gorton vent. Then adjust for where the radiator actually sits — the math gets you close, geography finishes the job.

The radiator

Equivalent direct radiation — count the sections and look them up, or measure.

Sets the air volume per square foot EDR. Cast-iron tube (circa 1930) at 0.013 cu ft/EDR is the common case.

The runout

The runout has to be filled with steam too, and it tries to steal some on the way.

Conditions

Higher pressure pushes more air through the same vent, so the same radiator takes a smaller vent at 3 oz than at 1 oz.

Three minutes is the working default in the source method.

Use the math answer as-is.

Air to move

Total air
0.803cu ft
Required venting rate
0.268CFM
SourceRatecu ft
Radiator0.013 /EDR0.520
Runout (1-1/2")0.0141 /ft0.283

Vent recommendation

Capacities read from the 1 oz column.

Install

Gorton C

Straight from the math, with no geography adjustment.

Install on radiators farthest from the boiler, and in coldest rooms (for example, third floor radiators).” — Gorton

The required rate sits close to the Gorton C ceiling. The source method bumps a vent up a size in exactly this situation when the radiator is any distance from the main.
Gorton ventCFM @ 1 ozVerdict
Gorton #40.025Too small
Gorton #50.080Too small
Gorton #60.150Too small
Gorton C0.270Recommended
Gorton D0.330Enough capacity

Radiator vent capacities

CFM at boiler pressure, as published.

Vent1 oz2 oz3 ozGorton's own rating
Gorton #40.0250.0400.055
Gorton #50.0800.1300.160Equal to 4 ordinary type air valves.
Gorton #60.1500.2350.300Equal to 8 ordinary type air valves.
Gorton C0.2700.4500.570Equal to 15 ordinary type air valves.
Gorton D0.3300.5400.700Equal to 27 ordinary type air valves.

The CFM columns are measured data from the HeatingHelp capacity chart. The right-hand column is Gorton's own wording — “equal to N ordinary type air valves” — reproduced as published. It is not the basis of any calculation here, because an “ordinary type air valve” has no defined flow rate.

Air per square foot EDR

By radiator construction.

Radiator typecu ft / EDR
Cast-iron tube (circa 1930)0.013
Cast-iron flue (antique radiators)0.029
Cast-iron wall- or ceiling-mounted0.028
Cast-iron column (circa 1900)0.025
Cast-iron thin tube (as made today)0.009
Cast-iron radiant radiator (5" deep)0.008
Cast-iron baseboard (10"-high)0.07
Cast-iron convector (in cabinet)0.0003
Unit heater0.0002

Worked example from the source

40 sq ft EDR cast-iron tube radiator, 20 ft of 1-1/2" runout, 1 oz, three minutes:

  • runout 20 × 0.014 = 0.28 cu ft
  • radiator 40 × 0.013 = 0.52 cu ft
  • total 0.80 cu ft ÷ 3 min = 0.26 CFM

A Gorton C passes 0.270 CFM at 1 oz, so it covers it — but only just, and the radiator is not close to the main. The source blends in geography and raises it to a Gorton D. Set the calculator to those inputs and you will see the same path.

Method and sources

  1. Radiator air = EDR × cubic feet per EDR for its construction.
  2. Runout air = length × cubic feet per linear foot (Schedule 40).
  3. Required rate (CFM) = (radiator + runout) ÷ target minutes.
  4. Pick the smallest Gorton vent that meets the rate at the working pressure, then adjust up or down for geography.

One vent that should stay small

Never oversize the vent on the radiator in the thermostat's room. Heating it first tells the thermostat the whole building is warm and shuts the boiler off early.